NCK alarms
06/2009 Overview of alarms
2-99
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
- AXIS: Property: Axis addresses, value range: Axis names only
- FRAME: Property: Geometric information, value range: As for axis paths
Overview of type conversions:
- from REAL to: REAL: yes, INT: yes*, BOOL: yes1), CHAR: yes*, STRING: -, AXIS: -, FRAME: -
- from INT to: REAL: yes, INT: yes, BOOL: yes1), CHAR: if value 0 ...255, STRING: -, AXIS: -, FRAME:
-
- from BOOL to: REAL: yes, INT: yes, BOOL: yes, CHAR: yes, STRING: -, AXIS: -, FRAME: -
- from CHAR to: REAL: yes, INT: yes, BOOL: yes1), CHAR: yes, STRING: yes, AXIS: -, FRAME: -
- from STRING to: REAL: -, INT: -, BOOL: yes2), CHAR: only if 1 character, STRING: yes, AXIS: -,
FRAME: -
- from AXIS to: REAL: -, INT: -, BOOL: -, CHAR: -, STRING: -, AXIS: yes, FRAME: -
- from FRAME to: REAL: -, INT: -, BOOL: -, CHAR: -, STRING: -, AXIS: -, FRAME: yes
1) Value <> 0 corresponds to TRUE, value ==0 corresponds to FALSE.
2) String length 0 => FALSE, otherwise TRUE.
3) If only 1 character.
It is not possible to convert from type AXIS and FRAME nor into type AXIS and FRAME.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Modify the program section such that the value range is not exceeded, e.g. by a modified variable def-
inition.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
14097 [Channel %1: ] Block %2 string cannot be converted to AXIS type
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: The called function AXNAME - conversion of the transferred parameters of the STRING type to an
axis name (return value) of the AXIS type - has not found this axis identifier in the machine data.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Please inform the authorized personnel/service department. Check the transferred parameter (axis
name) of the function AXNAME to determine whether a geometry, channel or machine axis of this
name has been configured by means of the machine data:
MD10000 $MN_AXCONF_MACHAX_NAME_TAB
MD20060 $MC_AXCONF_GEOAX_NAME_TAB
MD20080 $MC_AXCONF_CHANAX_NAME_TAB
Select the transfer string in accordance with the axis name, and change the axis name in the machine
data if necessary. (If a change of name is to take place via the NC part program, this change must first
be validated by means of a "POWER-ON").
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
14098 [Channel %1: ] Block %2 conversion error: no valid number found
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: The string is not a valid INT or REAL number.
Reaction: Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
Remedy: Modify part program. If it is an entry, then you can check whether the string is a number via the preset
function ISNUMBER (with the same parameter).
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program