Overview of alarms 06/2009
NCK alarms
2-138
© Siemens AG 2009 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2009
Possible actions are: mode change, SlashOn/Off, overstoring.
Reaction: Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Initiate a block change and repeat the action.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
16932 [Channel %1: ] Conflict when activating user data type %2
Parameters: %1 = Channel number
%2 = Data type
Definitions: The "activate user data" function (PI service _N_SETUDT) modifies a data block (tool offset, settable
zero offset or base frame) which is also written by the NC blocks in preparation.
In the event of a conflict, the value entered by the HMI is reset.
Parameter %2 specifies which data block is affected:
1: Active tool offset
2: Base frame
3: Active zero offset
Reaction: Alarm display.
Remedy: Check the inputs on the HMI and repeat if necessary.
Program Con-
tinuation:
Clear alarm with the Delete key or NC START.
16933 [Channel %1: ] Interrupt treatment: action %2<ALNX> not allowed in the
current state
Parameters: %1 = Channel number
%2 = Action number/action name
Definitions: If a temporary standstill has occurred because of a Reorg event across block boundaries, it is possible
that a block without Reorg capability has been loaded. In this situation, it is unfortunately necessary
to abort the Reorg event handling! Reorg events are, e.g. abort subprogram, delete distance-to-go
and interrupts.
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: Abort program with the RESET key.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program
16934 [Channel %1: ] Interrupt treatment: action %2<ALNX> not possible due to
stop
Parameters: %1 = Channel number
%2 = Action number/action name
Definitions: Reorg events are, e.g. abort subprogram, delete distance to go and interrupts, axis exchange, termi-
nation of follow-up mode. Two Reorg events overlap in this situation. The 2nd Reorg event coincides
with the 1st block generated by the previous event. (e.g. an axis exchange is induced twice in rapid
succession). Axis exchange leads to Reorg in the channels in which an axis is removed without prep-
aration. This block must be stopped in the above sequence in order to prevent the interpolator buffer
from overflowing. This can be achieved by pressing the Stop or StopAll key, configuring an alarm with
INTERPRETERSTOP or by decode single block.
Reaction: NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy: The program must be aborted with Reset.
Program Con-
tinuation:
Clear alarm with the RESET key. Restart part program