NCK alarms/ISO alarms
06/2007 Overview of alarms
2-103
" Siemens AG 2007 All Rights Reserved
SINUMERIK 802D sl, Diagnostics Manual, 06/2007Edition
12530 Channel %1 block %2 invalid index for %3
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Source string
Definitions: In macro definitions, an attempt was made to define a G function with more than 3 decades or an M
function with more than 2 decades as identifier of the macro.
Example
DEFINE G4444 AS G01 G91 G1234
DEFINE M333 AS M03 M50 M99
M17
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Key: Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM
CORRECT. The correction pointer positions on the incorrect block. Modify the macro definition in
accordance with the Programming Guide.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
12540 Channel %1 block %2 Block is too long or too complex
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: The maximum internal block length after translator processing must not exceed 200 characters.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM COR-
RECT. The correction pointer positions on the incorrect block.
Divide up the program block into several subblocks.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
12550 Channel %1 block %2 name %3 not defined or option/function not
activated
Parameters: %1 = Channel number
%2 = Block number, label
%3 = Source symbol
Definitions: The identifier displayed has not been defined before being used.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy: Press the NC Stop key and select the function "Correction block" with the softkey PROGRAM COR-
RECT. The correction pointer positions on the incorrect block.
- Correct the used name (typing error)
- Check the definition of variables and subroutines
- Check the options.
Program Con-
tinuation:
Clear alarm with NC START or RESET key and continue the program.
12552 Channel %1 block %2 tool/magazine OEM parameter not defined. Option
not set. Option not set.
Parameters: %1 = Channel number
%2 = Block number, label
Definitions: The programmed $TC_... Cx system variable is not known in the control.
Reaction: Correction block is reorganized.
Interface signals are set.
Alarm display.