10 How to Load New Firmware
B73
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
10 How to Load New Firmware
Requirements
You download new firmware to a SIMATIC NET CP using the firmware loader
shipped with STEP 7 / NCM S7.
Requirements for downloading
S To download firmware, you require an Industrial Ethernet CP module in the
PG/PC (for example, CP 1613) or a normal Ethernet module with the “Softnet”
software package.
S The S7-ONLINE interface must be set to the “ISO Industrial Ethernet”
protocol. It is not possible to download using TCP/IP (and therefore not to other
networks).
How to download new firmware
You can download via the PROFINET interface or the gigabit interface of the CP.
Always use the active MAC address on the CP interface you use to load the
firmware!
LEDs to indicate the CP mode
The different combinations of the LEDs on the front panel indicate the status:
Table 10-1
SF
(red)
BF1 + BF2
(red)
RUN
(green)
STOP
(yellow)
CP operating mode
Downloading firmware.
Firmware was successfully downloaded.
Firmware could not be downloaded.
Legend: (colored) on off (colored) flashing ” any
What to do if a download is interrupted
Disturbances or collisions on the network can lead to packets being lost. In such
cases, this can lead to an interruption of the firmware download. The firmware
loader then signals a timeout or negative response from the module being loaded.
In this case, turn the station off and on again and repeat the download.