3 Installation and Commissioning
B22
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
Module replacement: Special feature with PROFINET CBA and with IT functions
For PROFINET CBA, the interconnection information is stored on the CPLUG.
The file system for the IT functions is also stored on the C-PLUG. The following
must therefore be distinguished when replacing a module:
S CPLUG of the previous module is used
In this case, the CBA interconnection information and the data in the file system
on the CPLUG are available directly.
Although a diagnostic buffer entry is generated indicating that the C-PLUG
comes from a different device type, you can nevertheless continue to use the
C-PLUG from the GX21 device type in the new device (GX30).
S A new CPLUG is used
In this case, you will need to reload the configuration with STEP 7 and the CBA
interconnection information with SIMATIC iMap.
Module replacement: Special feature of IP address assignment from a DHCP
server
During configuration of the CP you can specify the IP configuration in the
properties dialog; one option is to obtain the IP address from a DHCP server.
Notice
When replacing modules, remember that the factory-set MAC address of the new
module is different from the previous module. When the factory-set MAC address
of the new module is sent to the DHCP server, this will return either a different or
possibly even no IP address.
Ideally, you should therefore configure IP as follows:
Always configure a client ID if you want to obtain the same IP address from the
DHCP server after replacing the module.
If you have configured a new MAC address instead of the factory-set MAC
address (generally the exception), the DHCP server always receives the
configured MAC address and the CP obtains the same IP address as the replaced
module.
Obtaining the IP address from DHCP is only possible on the PROFINET interface
ports and not on the gigabit interface.