5 Performance Data / Operation
B−34
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
Execution times of the FCs PNIO_SEND / PNIO_RECV
The calculation of the reaction times with PROFINET IO is determined by the
execution time of the function blocks required on the S7-300 CPU (PNIO_SEND,
PNIO_RECV).
Table 5-8
Component
Explanation / values
Execution time on the CPU
315-2DP
(6ES7 315-2EG10-0AB0)
per PNIO_SEND block call:
S < 1 ms at 240 bytes
per PNIO_RECV block call:
S < 1 ms at 240 bytes
Execution time on the CPU
317-2PN/DP
(6ES7 317-2EJ10-0AB0)
per PNIO_SEND block call:
S < 0.8 ms at 240 bytes
per PNIO_RECV block call:
S < 0.8 ms at 240 bytes
5.4.2 How PROFINET IO devices start up with a large operational
configuration
When operating the module with a large configuration (up to 48 communication
connections and up to 128 PROFINET IO devices), it may take several minutes
when the station starts up before all PROFINET IO devices have received
configuration data from the PROFINET IO controller. The IE/PB Link PN IO
operating as a PROFINET IO device is particularly affected by this.
To avoid the CPU stopping the distribution of configuration data in this situation, it
may be necessary to increase the monitoring times on the CPU (Properties dialog,
“Startup” tab).
5.4.3 Operating PROFINET IO alongside other services
Sporadically used services
Please remember the following when you use functions that affect the
configuration of the mode alongside PROFINET IO (FB55; Primary Setup Tool,
STEP 7, NCM Diagnostics):
Notice
These functions can influence operation with PROFINET IO to such an extent that
an interruption of the cyclic I/O data exchange of the PROFINET IO devices
lasting several seconds may result.