6 Using the CP for PROFINET CBA
B−48
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
Downloading configuration data
When using PROFINET CBA, downloading configuration data depends on the
component type of the S7-300 station, as follows:
S S7-300 station as singleton component
Step Explanation / meaning
1. S Downloading with STEP 7
Download the user program and configuration data to the S7-300 station with
STEP 7.
2. Downloading the interconnection information of the process inputs and process
outputs to the PROFINET CBA components over the Ethernet port with SIMATIC
iMap.
S S7-300 station as standard component
Step Explanation / meaning
1. S Downloading with SIMATIC iMap
Download the user program and configuration data to the S7-300 station with
SIMATIC iMap.
2. Downloading the interconnection information of the process inputs and process
outputs to the PROFINET CBA components over the Ethernet port with SIMATIC
iMap.
Caution
If problems occur while downloading interconnections from SIMATIC iMap, for
example power down on the target station, it is not always possible to download
the interconnections again when the power returns.
If this error occurs, SIMATIC iMap reports the station as being unreachable.
Remedy:
Using the PG command, change the CP 343-1 from STOP to RUN to bring the
target station back an operational status and to allow the interconnections to be
downloaded again from SIMATIC iMap.
Device diagnostics in SIMATIC iMap
In online view of SIMATIC iMap, you can use diagnostic functions and, for
example, read out device and functional information.
Commentaires sur ces manuels