9 Further Notes on Operation
B58
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
9 Further Notes on Operation
9.1 Memory reset
Available functions
The CP has a two-level function available for resetting memory:
S Clear / reset
Following this memory reset, the CP retains the default MAC addresses and the
retentive parameters. The CP is therefore immediately ready for downloads
using the IP address.
The retentive parameters include:
IP address, subnet mask and, if applicable, router address
LAN settings
PROFINET CBA interconnections
S Resetting to factory settings
After the memory reset, the CP retains only the two factory-set MAC addresses
(as shipped).
How to use the function
You can start the memory reset functions in STEP 7.
S Clear / reset
In STEP 7/HW Config with PLC
"
Clear/Reset
or
In STEP 7 / NCM Diagnostics with Operating Mode
"
Clear/Reset Module
S Factory defaults reset
In STEP 7 / NCM Diagnostics with Operating Mode
"
Reset to Factory
Defaults
Behavior after memory reset
The CPU in the S7 station does not recognize that the CP memory was reset. The
CP therefore changes to the “stopped with error” state (see Chapter 4).
The configuration data must then be reloaded.
if the configuration data are stored on the CPU, you can start a download with
power down/up.