5 Performance Data / Operation
B28
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
5 Performance Data / Operation
Note
Measurements of transmission and reaction times in Ethernet, PROFIBUS and
PROFINET networks for a series of configurations can be found on the Internet at
the following address:
http://www.siemens.com/automation/pd
5.1 Number of possible connections over Ethernet
Table 5-1
Characteristic Explanation / values
Permitted number of simultaneous connections in
total over Industrial Ethernet
48 maximum
Example of maximum load
You can, for example, operate:
32 S7 connections
2 ISO-on-TCP connections
8 TCP connections
6 UDP connections
Also:
S Other TCP connections for Web diagnostics and FTP server mode
S As PROFINET IO device:
1 PROFINET connection to a PROFINET IO controller
and/or
S As PROFINET IO controller:
PROFINET connections to PROFINET IO devices