3 Installation and Commissioning
B21
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
CPLUG formatting
Use only CPLUGs that are formatted for the CP 3431. CPLUGs that have
already been used and formatted in other device types must first be formatted for
the CP 3431 device type.
You do this with STEP 7 / NCM Diagnostics. For more detailed information, refer to
the online help in the topic “General Diagnostics Functions C-PLUG Diagnostics
Object”.
After formatting, all data areas are deleted on the C-PLUG. Project engineering is
adopted only after reloading or after turning on the power supply again.
Removing the C-PLUG
It is only necessary to remove the CPLUG if a fault occurs on the basic device
(see Figure 3-2).
Notice
The CPLUG must be removed only when the power is off!
Diagnostics
Inserting a CPLUG containing the configuration of an incompatible device type,
accidentally removing the CPLUG or general malfunctions of a CPLUG are
signaled by the diagnostic mechanisms of the host device (SFLED red).
3.3 Module replacement without PG
General procedure
The project engineering data for the CP is stored optionally on the CPU or on the
CP or in the CPLUG of the CP; this means that the module can be replaced with
the module of the same type (identical order number) without a PG.
If you replace the module with the predecessor module
6GK7 3431GX210XE0, the gigabit interface is deactivated.
For information on replacing previous modules, refer to the section “Compatibility”
in Chapter 8.