9 Further Notes on Operation
B64
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
9.4 IP configuration
9.4.1 Configured S7 connections cannot be operated if the IP
address is assigned over DHCP
Notice
If you obtain the IP address over DHCP, any S7 connections you may have
configured will not work. Reason: The configured IP address is replaced by the
address obtained over DHCP during operation.
Obtaining the IP address from DHCP is only possible on the PROFINET interface
and not on the gigabit interface.
9.4.2 Detection of double IP addressing in the network
To save you time-consuming troubleshooting in the network, the CP detects double
addressing in the network.
The reaction of the CP when double addressing is detected varies as follows:
S CP during startup
When the CP starts up (after power down or after the initial addressing), the CP
queries its own IP address on the network. If there is a response, the CP does
not start up! The error is indicated by an LED (“STOP with internal error” is
displayed) and an entry is made in the internal diagnostic buffer.
The CP remains in STOP mode.
When you eliminate the cause by removing the device with the same IP address or
changing its address, you must then restart the CP.
S CP in RUN mode
In RUN, the CP also sends this query at intervals of one minute to detect
double IP addresses.
If a double IP address is detected, the CP also reports this via the LEDs (BUSF
LED) and generates an entry in the diagnostic buffer.
The CP remains in RUN mode.