Siemens SIMATIC NET CP 343-1 Manuel d'utilisateur Page 29

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 80
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 28
5 Performance Data / Operation
B29
CP 343-1 Advancedfor Industrial Ethernet / Manual Part B
Release 06/2008
C79000-G8976-C202-04
5.2 Characteristic data for S7 communication
Table 5-2
Characteristic Explanation / values
Number of connections for S7 communication on
Industrial Ethernet
in each case, up to
S 16 Operator control and monitoring functions
(HMI)
S 16 S7 connections configured at one end
S 16 S7 connections configured at both ends
The number depends on the CPU type being used.
Please refer to /1/ for the values for your CPU.
LAN interface data field length generated by CP
per protocol data unit
S sending
S receiving
240 bytes / PDU
240 bytes / PDU
Execution times of the FBs for S7 connections
To calculate the CPU cycle times (OB1) with S7 connections, the execution time
for the function blocks (FBs PUT, GET, USEND, URCV, BSEND, BRCV) required
for processing on the S7-300 / C7-300 CPU is the decisive factor.
Table 5-3
Execution time on the CPU per block call
Block type PUT GET USEND URCV BSEND BRCV
Data length <=160 bytes <=16 KB
CPU 314C-2 DP
(6ES7 314-6CF00-0AB0)
<4.9 ms <4.6 ms <4.4 ms <4.8 ms <4.7 ms <4.9 ms
CPU 317-2 PN/DP
(6ES7 317-2EJ10-0AB0)
<1.1 ms <1.4 ms <1.3 ms <1.5 ms <1.4 ms <1.9 ms
Vue de la page 28
1 2 ... 24 25 26 27 28 29 30 31 32 33 34 ... 79 80

Commentaires sur ces manuels

Pas de commentaire