Installing
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
40 Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
EMC-compliant installation of Power Modules in degree of protection IP20
The EMC-compliant installation of power modules is shown in the following diagram using
two examples.
Example for a connection without a
shield plate via an external filter
Example for a connection with a shield plate, directly to
the line supply
Line supply connection
Motor connection
Metal mounting plate (unpainted and with a good electrical conductivity)
Cable clamps for a good conductive electrical connection through a large surface area
between the shield and mounting plate or shield plate.
Shielded cable for the motor connection
Shield plate
Unshielded cable for connection directly to the line supply
Shielded cable for connection to the line supply via an external filter.
Note
An unshielded cable for the line connection should be used for Power Modules with
integrated filter. Power Modules, which are connected to the line supply via an external filter,
require a shielded cable between the line filter and Power Module.