Functions
7.4 Setpoint sources
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
161
Table 7- 17 Extended setup of motorized potentiometer
Parameter Description
p1030 Configuration of the MOP, parameter value with four independently adjustable bits
00 to 03 (factory setting 00110 bin)
Bit 00: Save setpoint after switching off motor
0: After the motor is switched on, p1040 is specified as the setpoint
1: Setpoint is saved after the motor is switched off and set to the saved value once it
is switched on
Bit 01: Configure ramp-function generator in automatic mode (1-signal via BI: p1041)
0: No ramp-function generator in automatic mode (ramp-up/-down time = 0)
1: With ramp-function generator in automatic mode
In manual mode (0-signal via BI: p1041) the ramp-function generator is always active
Bit 02: Configure initial rounding
0: No initial rounding
1: With initial rounding. The initial rounding is a sensitive way of specifying small
setpoint changes (progressive reaction when keys are pressed).
Bit 03: Store setpoint in power-independent manner
0: No power-independent saving
1: Setpoint is saved in the event of a power failure (bit 00 = 1)
Bit 04: Ramp-function generator always active
0: Setpoint is only calculated with enabled pulses
1: Setpoint is calculated independent of the pulse enable (this setting is required if the
energy-saving mode has been selected).
p1035 Signal source to increase setpoint (factory setting 0)
Automatically pre-assigned during commissioning, e.g. with the button on the
Operator Panel
p1036 Signal source to reduce setpoint (factory setting 0)
Automatically pre-assigned during commissioning, e.g. with the button on the
operator panel
p1037 Maximum setpoint (factory setting 0 rpm)
Automatically pre-assigned during commissioning
p1038 Minimum setpoint (factory setting 0 rpm)
Automatically pre-assigned during commissioning
p1039 Signal source to invert minimum and maximum setpoints (factory setting 0)
p1044 Signal source for set value (factory setting 0)
For more information about the motorized potentiometer, see the List Manual (function
diagram 3020 and the parameter list).
Interconnecting the motorized potentiometer with the setpoint source
You have two options for interconnecting the motorized potentiometer with the setpoint
source:
1. Using p0015, select a configuration that is suitable for your application.
Please refer to the section titled Select interface assignments (Page 46) to find out which
config
urations are available for your inverter.
2. Interconnect the main setpoint with the motorized potentiometer by setting p1070 to
1050.