Appendix
A.1 Application Examples
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
285
Table A- 3 Assignment of the control bits in the inverter to the SIMATIC flags and inputs
HEX BIN Bit in
STW1
Significance Bit in
MW1
Bit in
MB1
Bit in
MB2
Inputs
0 0 ON/OFF1 8 0 E0.0
1 1 ON/OFF2 9 1
1 2 ON/OFF3 10 2
E
1 3 Operation enable 11 3
1 4 Ramp-function generator enable 12 4
1 5 Start ramp-function generator 13 5
1 6 Setpoint enable 14 6
7
0 7 Acknowledge fault 15
7 E0.6
0 8 Jog 1 0 0
0 9 Jog 2 1 1
1 10 PLC control 2 2
4
0 11 Setpoint inversion 3 3
0 12 Irrelevant 4 4
0 13 Motorized potentiometer ↑ 5 5
0 14 Motorized potentiometer ↓ 6 6
0
0 15 Data set changeover 7 7
Vue de la page 286