Introduction
1.5 Extended scope for adaptation
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
19
Parameter Description
P20032 = 5 The AND logic block is enabled by assigning to runtime group 5 (time
slice of 128 ms)
P20033 = 440 Run sequence of the AND logic block within runtime group 5 (processing
after the time block)
P20159 = 5000.00 Setting the delay time [ms] of the time module: 5 seconds
P20158 = 722.0 Connect the status of DI 0 to the input of the time block
r0722.0 = Parameter that displays the status of digital input 0.
P20030 [0] = 20160 Interconnecting the time block to the 1st input of the AND
P20030 [1] = 722.1 Interconnecting the status of DI 1 to the 2nd AND input
r0722.1 = Parameter that displays the status of digital input 1.
P0840 = 20031 Interconnecting the AND output to the control command ON/OFF1
Explanation of the example using the ON/OFF1 command
Parameter P0840[0] is the input of the "ON/OFF1 command" block of the converter.
Parameter r20031 is the output of the AND block. To interconnect the ON/OFF1 command
with the output of the AND block, set P0840 to 20031.
Index [1]
Index [2]
Index [3]
p20030
Index [0]
p0840[0] = 20031
ON/
OFF1
p0840
Index [0]r20031
&
AND 0
Figure 1-5 Interconnecting two BICO blocks by setting p0840[0] = 20031
Principle when connecting BICO blocks using BICO technology
An interconnection between two BICO blocks comprises a connector or binector and a BICO
parameter. The interconnection is always established from the perspective of the input of a
particular BICO block. This means that the output of an upstream block must always be
assigned to the input of a downstream block. The assignment is always made by entering
the number of the connector/binector from which the required input signals are read in a
BICO parameter.
This interconnection logic involves the question: where does the signal come from?