Adapt terminal strip
5.5 Analog outputs
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
99
Defining the analog output function
You define the analog output function by interconnecting parameter p0771 with a connector
output of your choice. Parameter p0771 is assigned to the particular analog input via its
index, e.g. parameter p0771[0] is assigned to analog output 0.
Table 5- 9 Connector outputs (CO) of the inverter (selection)
CO Significance CO Significance
r0021 Actual frequency r0026 Actual DC link voltage
r0024 Output actual frequency r0027 Output current
r0025 Output actual frequency
A complete list of the connector outputs is provided in the List Manual.
Table 5- 10 Example:
 $2
r0027
|i|
27
p0771
Output the inverter output current via analog output 0.
For more information, see the parameter list and the function block diagrams 9572 ff of the
List Manual.
Advanced settings
You can manipulate the signal that you output via an analog output, as follows:
Absolute-value generation of the signal (p0775)
Signal inversion (p0782)
Additional information is provided in the parameter list of the List Manual.