Siemens SINAMICS G120 Instructions d'exploitation Page 190

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 304
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 189
Functions
7.9 Application-specific functions
Inverter with CU240B-2 and CU240E-2 Control Units
188 Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
Main features of the braking functions
DC braking
The motor converts the regenerative power into
heat.
Advantage:
The motor brakes without the
inverter having to process the regenerative
energy
Disadvantages:
significant increase in the
motor temperature; no defined braking
characteristics; no constant braking torque; no
braking torque at standstill; regenerative
power is lost as heat; does not function when
the line supply fails
Compound braking
The motor converts the regenerative power into
heat.
Advantage:
Defined braking characteristics,
the motor brakes without the inverter having to
convert any regenerative energy
Disadvantages:
significant motor temperature
rise; no constant braking torque; regenerative
power is dissipated as heat; does not function
when the line supply fails
a
a
0RWRU
%UDNH
SRZHU
/RDG
,QYHUWHU
0
Dynamic braking
The inverter converts the regenerative
power into heat using a braking resistor.
Advantages:
defined braking
characteristics; no additional motor
temperature increase; constant
braking torque; in principle, also
functions when the power fails
Disadvantages:
Braking resistor
required; regenerative power is
dissipated as heat
a
a
,QYHUWHU
%UDNLQJUHVLVWRU
%UDNLQJUHVLVWRU
0RWRU
%UDNH
SRZHU
/RDG
,QYHUWHU
%UDNLQJ
FKRSSHU
0
Vue de la page 189
1 2 ... 185 186 187 188 189 190 191 192 193 194 195 ... 303 304

Commentaires sur ces manuels

Pas de commentaire