Functions
7.10 Safe Torque Off (STO) safety function
Inverter with CU240B-2 and CU240E-2 Control Units
230 Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
Switch off the inverter supply voltage.
Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
again. Your settings only become effective after this power-on reset.
7.10.7.6 Multiple assignment of the DI
Check whether the digital inputs used as fail-safe input are also assigned a further
function.
NOTICE
Both, the assignment of digital inputs with the selection of a safety function or with a
"standard" function can lead to an unexpected behavior of the motor.
Remove multiple assignments of the digital inputs:
Figure 7-31 Example: automatic assignment of digital inputs DI 4 and DI 5 with STO