Appendix
A.1 Application Examples
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
291
Activate the tab "Address
configuration".
Select line 1.
Open the dialog box in which you
define the Publisher and the address
area to be transferred.
Select DX for direct data exchange
Select the PROFIBUS address of drive 1
(publisher).
In the address field, select the start
address specifying the data area to be
received from drive 1. In the example, these
are the status word 1 (PZD1) and the speed
actual value with the start address 256.
Close both screen forms with OK. You have now defined the value range for slave-to-slave
communication.
In the slave-to-slave communication, drive 2 receives the sent data and writes this into the
next available words, in this case, PZD3 and PZD4.
Settings in drive 2 (subscriber)
Drive 2 is preset in such a way that it receives its setpoint from the higher-level control. In
order that drive 2 accepts the actual value sent from drive 1 as setpoint, you must set the
following:
In drive 2 ,set the PROFIdrive telegram selection to "Free telegram configuration with
BICO" (p0922 = 999).
In drive 2, set the source of the main setpoint to p1070 = 2050.3.