Siemens SINAMICS G120 Instructions d'exploitation Page 284

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 304
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 283
Appendix
A.1 Application Examples
Inverter with CU240B-2 and CU240E-2 Control Units
282 Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
A.1.1.5 Insert the frequency converter into the STEP 7 project
Install the GSD of the converter in STEP 7 via HW Config (Menu "Tools - Install GSD
files").
Once the GSD has been installed, the converter appears under "PROFIBUS DP -
Additional field devices" in the hardware catalog of HW Config.
Drag and drop the converter into the PROFIBUS network. Enter the PROFIBUS address
set at the converter in HW Config.
The telegram type defines which data is exchanged between the control and converter.
Insert the required telegram type from the HW catalog by dragging and dropping into slot
1 of the converter.
You can find more information on the telegram types in Chapter Cyclic communication
(Page 105).
Sequence when assigning the slots
1. PROFIsafe module (if one is being used)
Information on connecting the converter via PROFIsafe can be found in the "Safety
Integrated Function Manual".
2. PKW channel (if one is used)
3. Standard, SIEMENS or free telegram (if one is used)
4. Slave-to-slave module
If you do not use one or several of the modules 1, 2 or 3, configure the remaining modules
starting with the 1st slot.
Vue de la page 283
1 2 ... 279 280 281 282 283 284 285 286 287 288 289 ... 303 304

Commentaires sur ces manuels

Pas de commentaire