Commissioning
4.5 Commissioning with STARTER
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
75
In the next step, we
recommend the setting
"Calculate motor data only".
In the next step, set the
check mark for "RAM to ROM
(save data in drive)" in order
to save your data in the
converter so that it is not lost
when the power fails.
If you exit the wizard, the
converter outputs alarm
A07791. You must now
switch-on the motor to start
motor data identification.