Configuring the fieldbus
6.1 Communication via PROFIBUS
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
109
6.1.4.2 Control and status word 3
The control and status words fulfill the specifications of PROFIdrive profile version 4.1 for
"speed control" mode.
Control word 3 (STW3)
Control word 3 has the following default assignment. You can change the assignment with
BICO technology.
Table 6- 8 Control word 3 and interconnection with parameters in the converter
Meaning
Bit Value
Telegram 350
Comments BICO interconnection
1)
0 1 Fixed setpoint, bit 0 p1020[0] = r2093.0
1 1 Fixed setpoint, bit 1 p1021[0] = r2093.1
2 1 Fixed setpoint, bit 2 p1022[0] = r2093.2
3 1 Fixed setpoint, bit 3
Selects up to 16 different fixed setpoints.
p1023[0] = r2093.3
4 1 DDS selection, bit 0 p0820 = r2093.4
5 1 DDS selection, bit 1
Changes over between settings for
different motors (drive data sets).
p0821 = r2093.5
6 Not used
7 Not used
8 1 Technology controller enable -- p2200[0] = r2093.8
9 1 DC braking enable -- p1230[0] = r2093.9
10 Not used
11 1 1 = Enable droop Enable or inhibit speed controller droop. p1492[0] = r2093.11
1 Torque control active 12
0 Speed control active
Changes over the control mode for vector
control.
p1501[0] = r2093.12
1 No external fault 13
0 External fault is active (F07860)
-- p2106[0] = r2093.13
14 Not used
15 1 CDS bit 1 Changes over between settings for
different operation interfaces (command
data sets).
p0811[0] = r2093.15
1)
If you switch from telegram 350 to a different one, then the converter sets all interconnections p1020, … to "0".
Exception: p2106 = 1.