Configuring the fieldbus
6.1 Communication via PROFIBUS
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
115
Example of read request for parameter P7841[2]
To obtain the value of the indexed parameter P7841, you must fill the telegram of the
parameter channel with the following data:
Request parameter value (field): Bits 15 … 12 in the PKE word:
Request identifier = 6
Parameter number without offset: Bits 10 … 0 in the PKE word:
Because you can only code parameter numbers from 1 … 1999 in the PKE, you must
deduct as large an offset as possible, a number divisible by 2000, from the parameter
number, and transfer the result of this calculation to the PKE word.
In our example, this means: 7841 - 6000 = 1841
Coding the offset of the parameter number in the page index byte of the IND word:
In this example: When offset = 6000, this corresponds to a page index value of 0x90.
Index of parameter in the subindex byte of the IND word:
In this example: Index = 2
Because you want to read the parameter value, words 3 and 4 in the parameter channel
for requesting the parameter value are irrelevant. They should be assigned a value of 0,
for example.
Table 6- 14 Request to read parameter P7841[2]
PKE (1st word) IND (2nd word) PWE (3rd and 4th words)
AK PNU (10 bits) Subindex
(H byte)
Page index
(L byte)
PWE1
(H word)
PWE2
(L word)
0x6 0 0x731 (decimal: 1841) 0x02 0x90 0x0000 0x0000
Rules for editing requests and responses
You can only request one parameter per transmitted telegram
Each received telegram contains only one response
The request must be repeated until the right response is received
The response is assigned to a request by means of the following identifiers:
Suitable response identifier
Suitable parameter number
Suitable parameter index IND, if required
Suitable parameter value PWE, if necessary
The complete request must be sent in a telegram. Request telegrams cannot be
subdivided. The same applies to responses.