54 Siemens Simatic S7 Driver Online Help
How It Works
The driver polls a datablock on the device and experiences a communication timeout.
The driver attempts to re-send the request to the process hardware. If SIMATIC NET
cannot send a message, the driver marks the datablock as failed and sends a message
to the next datablock in the queue.
If SIMATIC NET can send a message, the retry proceeds, and the driver continues to
send retry message until:
The driver poll (retries) the datablock the number of times configured for the
Retries property and still experiences a communication timeout.
SIMATIC NET becomes unable to send a message to the device.
In either case, the driver marks the datablock as failed and sends a message to the
next datablock in the queue. Any outstanding messages for the bad device are failed
immediately. Likewise, the driver sends any messages in the queue intended for the
bad device, and all new messages, once without retries. The driver continues this
process until the communication problem with the device is resolved.
The SI7 driver also executes its QuickFail logic if SIMATIC NET cannot send a retry
message. This happens when the connection or a transaction is bad.