34 Siemens Simatic S7 Driver Online Help
Forcing a Switch Between Primary and Back-up
Channels or Devices using FIX or iFIX
You can force the driver to toggle between the current and backup device when any
value is written to a Digital Output or Analog Output block. If the backup device is
only configured for use on the backup channel, the channel also switches. The driver
switches devices when you write a value to the block.
I/O address syntax: !SWITCH:NAME
where NAME is the name of the device you want to switch. You cannot switch only
from one channel to another.
See Also
Specifying I/O Addresses in Database Manager
Enabling or Disabling Channels, Devices or
Datablocks using FIX or iFIX
You can enable or disable a channel, device, or datablock by entering a special I/O
address into a Digital Output block. Write a value of 1 to the block to enable it, or
write a value of 0 to disable it.
I/O address syntax: !MODE:NAME
where NAME is the name of the channel, device, or datablock you want to enable or
disable.
See Also
Specifying I/O Addresses in Database Manager