166 Siemens Simatic S7 Driver Online Help
See Also
Forcing a Switch Between Primary and Back-up Channels or Devices using FIX or
iFIX | Enabling or Disabling Channels, Devices or Datablocks using FIX or iFIX |
Sending Multiple Writes to a Datablock
Specifying Signal Conditioning in Database
Manager
With the Database Manager Signal Conditioning field, you can specify the method
for converting raw data to a value that FIX/iFIX applications can use. Once you
select a signal conditioning, the driver scales (converts) the data to a value within the
specified range.
Unsigned 8- and 16-bit data types support all types of signal conditioning; signed 8-
and 16-bit values only support LIN signal conditioning. Other data types, such as
DWORD, DINT, REAL, ASCII or STRING, do not support signal conditioning.
Timers requires TBCD signal conditioning and counters require 3BCD signal
conditioning.
The type of signal conditioning you select must match the range of incoming values
from the process hardware. By matching the range of values in the process hardware,
you ensure the driver can properly convert the raw data values to the database block’s
EGU range. For example, if the incoming values are between 0 and 255, you would
select 8BN signal conditioning.
Signal
Conditioning
Type