Siemens SIMATIC NET Spécifications Page 232

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 268
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 231
222 Siemens Simatic S7 Driver Online Help
If the driver still does not load
Rename the default configuration file so the driver loads a blank
configuration. If the configuration file is corrupt, it may prevent the driver
from loading. You can retrieve a corrupted configuration file if you save it as
a .CSV file; otherwise, you have to rebuild the driver configuration.
See Also
The driver loads but does not start polling | Tools for Troubleshooting the SI7 I/O
Driver
The driver loads but does not start polling
If the driver loads but does not start polling
[1] Verify that the channels, devices, and datablocks are enabled. You can
examine these properties in the SI7 I/O Driver Power Tool.
[2] If FIX or iFIX is not your Human-Machine Interface (HMI) software, make
sure the Auto Start option is turned on:
[a] Select Setup from the Options menu. The Setup dialog box appears.
[b] Select the Advanced tab.
[c] Click the Auto Start On option from the Server area.
If you are starting the driver from FIX/iFIX
[1] Verify that IOCNTRL starts from the SCU. You should have a /a on the
command line for IOCNTRL to start the driver automatically.
[2] Specify a default path and configuration file name for the driver:
[a] Click Setup from the Options menu. The Setup dialog box appears.
[b] Select the Default Path tab.
[c] Enter the configuration file’s default name and default path in the fields
provided.
Vue de la page 231
1 2 ... 227 228 229 230 231 232 233 234 235 236 237 ... 267 268

Commentaires sur ces manuels

Pas de commentaire