UM344-2 ON-LINE AND OFF-LINE OPERATION
August 1995
5
-
19
5.1.3.3 Local Pushbutton
Damping Adjustment (Controller
OFF)
Adjusting the damping changes the value of the digital filter’s
time constant. An installed Digital Meter is recommended
for this procedure so that the damping values may be
monitored.
1. Activate the Pushbutton Damping Mode.
Simultaneously press and hold, for 5 seconds or more, the
FULLSCALE and ZERO pushbuttons, then release both
pushbuttons. Note the following.
The Damping Mode is automatically de-activated
when a 1 minute "mode active" period times-out. If
a change is not made, the present value is retained.
When both pushbuttons are pressed a "PB"
annunciator will appear on the Digital Meter. If the
pushbuttons have been held on for the required
minimum 5 seconds, when they are released, the
"PB" annunciator will remain on and the Digital
Meter will alternately display the letters "SEC" (for
seconds) and the present damping value in seconds.
2. Select a new damping value. The damping value choices
are: 0, 0.5, 1, 2, 5, 10, 20, 30, 60, 90, and 120 seconds.
Repeatedly press the ZERO pushbutton to step down or
the FULLSCALE pushbutton to step up through the list.
Select a time constant from the list that is closest to the
desired value.
3. Simultaneously press, then release, both pushbuttons. The
new value is stored in memory and normal operation is
restored.
4. Restore protective cover over pushbuttons.
5. To set damping without a digital meter activate the
pushbutton mode as described in step 1 above.
6. Repeatedly press the ZERO pushbutton at least ten times
to set the damping value to zero seconds.