UM344-2 ON-LINE AND OFF-LINE OPERATION
August 1995
NOTE
Function blocks are in an easy to use format with
configuration parameters grouped by like
function. Those supported are Sensor Input,
Operator Display, Transmitter ID, Output Block,
Alarm Block, SP Track & Hold, A/M Transfer
and Controller Block. Each is shown in
Appendix A.
7. Press SELECT (F4) to view or edit a function block’s
parameters. Pressing END (F3) will end configuration (see
step 4 above).
Go to the section for the selected function block (Sections 5.1.1.1
- 5.1.1.8).
5.1.1.1 Sensor Input Block
The following parameters can be changed: INPUT TYPE,
MEASURED VARIABLE (MV) UNITS, RANGE,
DAMPING, and BURNOUT DIRECTION.
1. Press SEL (F4) at the Sensor Input Block to display the Input
Type.
2. Press LAST OPTN (F1) or NEXT OPTN (F2) to scroll
through the Input Options: T/C, OHM, mV, RTD.
3. Press SEL/CONT (F4) to select the current parameter, and
continue to the next Input Type configuration parameter.
4. Press LAST OPTN (F1) or NEXT OPTN (F2) to scroll
through the Input Options.
5. Press SEL/CONT (F4) to select the current parameter, and
continue to the MEASURED VARIABLE UNITS Screen.
6. Press LAST OPTN (F1) or NEXT OPTN (F2) to scroll
through the units selections. These units are listed in
Appendix C under the Sensor Input Block description.
7. Press SEL/CONT (F4) to select the current parameter,
display the Range screen, and continue to the next
configuration parameter (go to step 8).
Pressing SEL/END (F3) will select the current parameter, end
configuration, and return to the On-Line Menu.
MEASURED VARIBLE
UNITS: deg F
LAST
NEXT
SEL/
SEL/
OPTN OPTN CONTEND
RANGE LO: 0.0000
deg F HI: 100.00
SEL/
SEL/
CONTENDEDIT INPUT
SNSR
INPUT TYPE: T/C
J THERMOCOUPLE
LAST NEXT
SEL/
SEL/
OPTN OPTN CONTEND