INITIAL TRANSMITTER SET-UP UM344-2
September 1995
SP TRACK & HOLD
Tracking Setpoint
PUSP
A/M TRANSFER
Power-Up Mode
Automatic Only
Power-Up Valve
CONTROLLER BLOCK
Controller ON/OFF
Controller Type
Action
Prop. Gain
Time-Integral
Time-Derivative
Derivative Gain
Manual Reset
Manual Reset Track
* For more detailed information on these function
blocks, refer to Section 5 and Appendix A.
3.5 CHECKING TRANSMITTER
OUTPUT
At this point, check to be sure that the transmitter is
reading the proper sensor input in the proper units.
1. Set the sensor input to the transmitter to a known
value either by adjusting the process variable to a
field mounted transmitter or the simulated input to a
bench test transmitter.
2. With the On-Line Menu displayed, press the gray
TRANS.VAR’s key on the MXC keypad to display
the VIEW WHICH VARIABLES screen.
3. Press one of the following keys depending upon
controller activation:
Controller Block ON: Press CONT (F2) to display
the controller variables.
P - Process
S - Setpoint
V - Valve
Controller Block OFF: Press XMTR (F1) to display
the process variables.
M - Measured Variable
I - Current (mA)
VIEW WHICH VARIBLES
XMTR CONT
END
P: 63.301%
S: 50.000%
V: 10.000%
END
M: 76.534 deg F
I: 4.8377 mA
P: 76.534 deg F
END