UM344-2 CALIBRATION AND MAINTENANCE
September 1995
NOTE
Removing a transmitter can interrupt power to other transmitters
powered from a common power source. Note the effect this can have
on process control and operation and, if necessary, follow the proper
procedures to shut down the process.
When disconnecting the SIGNAL leads, carefully insulate each lead as it
is removed to prevent accidental electrical shorts.
2. Remove the enclosure cap for access to the terminal compartment
3. Connect MXC and DMM (milliammeter) to the loop as shown in either Figure 6-1 or 6-2. Set DMM
to measure 4-20 mA.
Field Calibration Wiring - Open jumper at Circuit Junction.
4. Place loop in Manual mode.
5. Apply power to the Loop.
6. Establish communication between MXC and transmitter. Refer to Section 3.2 as necessary.
If the transmitter is configured for digital mode, reconfigure for analog mode by setting the short
address to zero (0). Refer to Section 5.1.1.3 as necessary.
7. At the Main Menu, select the CAL/TEST program.
Step through the MXC screens and use the PREV and NEXT
buttons to select the DAC OUTPUT calibration. Press SELECT
(F4).
The MXC will display the adjacent screen:
8. Press ENTER (F4).
The MXC will display:
9. Read the ammeter. It should indicate: 4.000 ±0.0048 mA.
10. If output is within limits, press QUIT (F3) and proceed to step 13.
If calibration is required, perform steps 11 and 12.
11. Respond to the prompt. Key in the current indicated by the ammeter and press ENTER (F4).
PRESSING ENTER WILL
SET TRANSMITTER
OUTPUT TO A- EN-
4.00 MA BORT TER
ENTER OUTPUT CURRENT
MA
EN-
< QUIT TER