UM344-2 INSTALLATION
September 1995
250
See
Note 2
MXC
See Note 4
See
Note 3
Notes:
1. The System Power Supply is shown separate from the host input device. In practice, it may be part
of the host input device. The host input device can be either a HART or non-HART signaling device,
a Primary Master or a Secondary Master.
2. Network resistance equals the sum of the barrier resistances and the current sense resistor.
Minimum value 250 Ohms; maximum value 1100 Ohms.
3. Connect the MXC (a Secondary Master) to the loop only in the non-hazardous location. The MXC
is a non-polar device.
4. Interconnect all cable shields and ground only at the power source.
5. For access to Model 344 terminals, remove shorter end cap.
6. Maximum loop cable length calculated by formula in Section 4.3.5.
+
_
+
_
System Power
Supply
Controller,
Recorder, or Other
1-5 Vdc Device;
See Note 1
See Note 5
Network
Junction
250
See
Note 2
Controller,
Recorder, or
Other 1-5 Vdc
Device; Note 1
MXC
Hazardous
Location
Non-Hazardous
Location
Supply and
Return Barriers
Shown Above
See Note 4
See
Note 3
See Note 5
See Note 6
_
+
+
_
System Power
Supply
See Note 6
Network for Hazardous Locations
Network for Non-Hazardous Locations
+
_ _
Signal Test
+
_
+
_
Signal Test
X02866S1
Model 344
Terminals
Model 344
Terminals
+