Installation and Maintenance
5.7 LED Displays and Troubleshooting
SIMATIC NET PROFIBUS Optical Link Module OLM V4.0
Operating Instructions, 01/2013, C79000-G8976-C270-03
41
LED display Possible causes Signaling
contact
lit green - The transmission rate was detected and the voltage supply is ok does not signal
not lit - Voltage supply outage (complete outage, with a redundant supply, outage
down of both supply voltages)
- Voltage supply connected wrongly
- Module defective
signals
flashes red Transmission rate not yet detected
- There is no transmitting bus node
- No connection to a partner module sending frames
- Transmit and receive fiber-optic cables are swapped over
- Transmission rate does not correspond to the PROFIBUS standard
- Only one single bus node is connected, which only sends token to itself. After
activation of a second bus node, the display must change (token frames are
not enough to set the transmission rate)
- The connected RS-485 segment is only terminated at one side
does not signal
System
flashes
red/green
Transmission rate detected but
- The slot time of the network could not be detected yet (network parameter
HSA set too low, there is no transmitting bus node)
- One optical channel is set to “redundant optical ring“ mode but the second
one is not (this mode must always be set on both optical channels)
- The value for the slot time of the network is set too low
does not signal
does not signal
lit yellow Signals are received on the RS-485 bus lines. does not signal CH1, CH0
electrical
not lit Bus node is not connected, does not signal
-Connected bus node is not turned on
- Interruption
5
of one or both cores of the RS-485 bus line
- Short circuit
1
or ground fault of cores of the RS-485 bus line
does not signal
flashes red/lit red Sporadic disturbances because of
- Insufficient shielding of the RS-485 bus cable
- Open bus cable, this means the RS-485 bus cable is only connected at one
end
- RS-485 segment is not terminated or only at one end
- Removal/insertion of an RS-485 bus terminal or terminating plug
Permanent problem because
- Cores A and B of the RS-485 bus cable have been swapped over
- Short circuit
1
on the RS-485 bus cable
- Transmission time exceeded due to a bus node in a bus segment connected
to channel 1 or 0
-Module and other bus nodes connected over channel 1 or 0, transmit at the
same time (e.g. because of duplicate address assignment or slot time set too
low or when restoring after segmentation in the optical line, see section 3.1.1 )
- RS-48
5 driver of the module defective (e.g. after lightning strike)
signals
does not signal
Mode “Bus with fiber-optic link monitoring” and “redundant optical ring“
CH2, CH3
optical
lit yellow PROFIBUS frames are received on the optical channel does not signal
5
Depends on the cable length between RS485 interface and fault, and on baud rate. Can vary from one example to another.