Network Topologies
3.3 Ring Topology
SIMATIC NET PROFIBUS Optical Link Module OLM V4.0
14 Operating Instructions, 01/2013, C79000-G8976-C270-03
Configuration 1 (see Figure 3-4, FOC1 < FOC2) , LED display:
1. Situation, no FOC interruption:
OLM 1 OLM 2
SystemLED = lit green SystemLED = lit green
CH1/0 LED = lit yellow CH1/0 LED = lit yellow
CH2 LED = lit yellow CH2 LED = is not lit
CH3 LED = is not lit CH3 LED = lit yellow
2. Fault, FOC1 interrupted:
OLM 1 OLM 2
System
LED = lit green
SystemLED = lit green
CH1/0 LED = lit yellow CH1/0 LED = lit yellow
CH2 LED = lit red CH2 LED = lit yellow
CH3 LED = lit yellow CH3 LED = lit red
3. Fault, FOC2 interrupted:
OLM 1 OLM 2
System
LED = lit green
SystemLED = lit green
CH1/0 LED = lit yellow CH1/0 LED = lit yellow
CH2 LED = lit yellow CH2 LED = lit red
CH3 LED = lit red CH3 LED = lit yellow
Configuration 2 (Figure 3-5, FOC1 < FOC2) , LED display:
1. Situation, no FOC interruption:
OLM 1 OLM 2
SystemLED = lit green SystemLED = lit green
CH1/0 LED = lit yellow CH1/0 LED = lit yellow
CH2 LED = lit yellow CH2 LED = lit yellow
CH3 LED = is not lit CH3 LED = is not lit
2. Fault, FOC1 interrupted:
OLM 1 OLM 2
SystemLED = lit green SystemLED = lit green
CH1/0 LED = lit yellow CH1/0 LED = lit yellow
CH2 LED = lit red CH2 LED = lit red
CH3 LED = lit yellow CH3 LED = lit yellow