SIMATIC NET PROFIBUS Optical Link Module OLM V4.0
Operating Instructions, 01/2013, C79000-G8976-C270-03
7
3 Network Topologies
3
Which network topologies can be implemented?
The following network topologies can be implemented with the PROFIBUS OLM:
Point-to-point connection
Bus (linear) topology
Star topology
Redundant optical ring
Combinations of these basic types are also possible. To set up the fiber-optic links of these
network topologies, cables with two optical fibers are used.
If a high degree of availability is required of the fieldbus network, this can be increased by
using a redundant network configuration, for example to allow continued communication if a
cable is broken.
Please note the following:
Single DTEs or complete PROFIBUS segments with a maximum of 31 nodes can be
connected to the electrical interface of the PROFIBUS OLM.
Use only fiber-optic cables in areas subject to heavy noise to avoid EMC problems
affecting the entire network.
Only OLMs of the same wavelength may be connected to each other optically:
– OLM / P11, OLM / P12 and OLM / P22 with each other
– OLM / G11, OLM / G12, OLM / G22, and OLM / G12 EEC with each other
– OLM / G11-1300 and OLM / G12-1300 with each other
Optical channels connected via fiber-optic cables must be set to the same mode.
Transitions between different OLM types are only possible via the RS-485 interface.
In the network topologies described below, the OLM / G12-EEC can be used everywhere
where an OLM / G12 can be used.