FS-250 Installation and Operation Manual
42
Addressable Device Circuit Wire Selection Guide
Each addressable device circuit must meet the following requirements:
Total loop resistance - 50 ohm maximum with 252 devices.(refer to following graph)
Total loop capacitance - 0.5uF max line to line and 1.0uF max line to shield
Line Resistance Graph
The terminal blocks of Siemens P2 devices are rated for a maximum of 14AWG wire.
110
130
260
10
240
120
230
260
100
250
90
180
220
80
240
210
70
200
60
180
50
170
170 230
40
160
160 220
190
100
30
150
Note: The total number of devices can not exceed 252.
The line resistance of each loop can also be calculated by using R=1260/N.
R is line resistance and N is the number of devices in the loop.