Siemens FS-250 Spécifications Page 12

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 68
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 11
FS-250 Installation and Operation Manual
6
outputs. It can also be programmed to silence Siemens sync horns while the sync strobes
remain on, using two wires. This requires a silenceable and non-silenceable input.
The PAD-3 also offers a 3 amp auxiliary output for driving other portions of your fire alarm
system.
P2 ADDRESSABLE DEVICES
FirePrint™ Smoke Detector
The control panel processor sends the sensitivity and pre-alarm settings to the detectors
and polls the detectors as to their status. The detector determines normal, trouble, pre-
alarm or alarm conditions and communicates the status to the control panel.
Variable Thesholds - The detectors can be set to operate in various pre-programmed
optimizations, depending on installation locations.
Operator Alerts - The control panel can trigger an alarm or trouble automatically on the
occurrence of a number of conditions of the detector. These include:
Maintenance alert
Pre-alarm alert
No response
Incorrect response
Heat Detectors
Addressable heat sensing detectors may be intermixed on the circuit for locations where
heat sensing may be the most effective detection mode. The heat detectors may be
programmed, through the control panel, for rate of rise operation.
Addressable Modules (Monitor and Control)
In addition to detectors, the circuit can communicate with addressable modules, allowing
initiating devices or notification appliances with local power sources, and supervising the
power sources.
Manual Stations
Addressable manual stations may be intermixed on the circuit with proper response
programmed into the control panel.
Programming P2 devices
P2 devices can be programmed in the following two ways:
DPU Device Programmer/Loop Tester - Refer to the DPU User’s Manual, P/N 315-
033260, for further information.
FS-250 Panel Keypad - Refer to Programmer’s Manual, P/N 315-049403, for detailed
information of system programming. Used only for field removal and reinstallation of
individual devices.