Siemens FS-250 Spécifications Page 42

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 68
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 41
FS-250 Installation and Operation Manual
36
P2 Addressable Device Wiring Diagrams
Refer to the instruction sheets packed with each device.
Detectors and modules may be wired together according to several NFPA defined wiring
styles. The wiring style that is appropriate for your installation should be determined from
the relevant building codes and the Authority Having Jurisdiction.
Style 4 wiring permits branching of circuit connections. The control equipment supervises
modules because they are active and must respond periodically to the control panel's
interrogation.
P2 ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA STYLE 4
Siemens P2 Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 252 devices per addressable device circuit. A
Maximum of 20 devices recommended per Isolator Module. A Maximum of 15 Isolator Modules per addressable device circuit.
SUPERVISED,
POWER LIMITED
TO OPTIONAL
BRANCH(ES) OF
LOOP CIRCUIT
Technical Manuals Online! - http://www.tech-man.com
Vue de la page 41
1 2 ... 37 38 39 40 41 42 43 44 45 46 47 ... 67 68

Commentaires sur ces manuels

Pas de commentaire