Siemens FS-250 Spécifications Page 21

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 68
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 20
FS-250 Installation and Operation Manual
15
Recall
To signal recall after a drill, proceed as follows:
Press "MENU".
At the next screen, select "More".
Select "RECALL".
At the next screen, select "Yes".
Operate ALARM SILENCE to terminate recall signal.
Pre-Alarm
A pre-alarm condition is annunciated by Pre-alarm LEDs and buzzers on the control
panel and LCD Annunciators and Remote Processors. The LEDs flash and buzzers are
on steady until acknowledgment.
Acknowledging the Pre-alarm condition puts LEDs on steady and buzzers off.
If pre-alarm has been acknowledged and restores to normal, the condition clears. If the
system proceeds into an alarm condition, the pre-alarm condition clears whether or not
it has been acknowledged and is replaced by alarm.
General Alarm
To activate a general alarm, proceed as follows:
Press "MENU".
On the MENU display, select "GENERAL ALARM".
At the next screen, select "Yes".
Silence and reset the system as with any alarm.
Alert
To activate alert alarm, proceed as follows:
Press "MENU".
On the MENU display, select "ALERT".
At the next screen, select "Yes".
Operate ALARM SILENCE to terminate alert signal.
Technical Manuals Online! - http://www.tech-man.com
Vue de la page 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 67 68

Commentaires sur ces manuels

Pas de commentaire