FS-250 Installation and Operation Manual
15
Recall
To signal recall after a drill, proceed as follows:
• Press "MENU".
• At the next screen, select "More".
• Select "RECALL".
• At the next screen, select "Yes".
• Operate ALARM SILENCE to terminate recall signal.
Pre-Alarm
• A pre-alarm condition is annunciated by Pre-alarm LEDs and buzzers on the control
panel and LCD Annunciators and Remote Processors. The LEDs flash and buzzers are
on steady until acknowledgment.
• Acknowledging the Pre-alarm condition puts LEDs on steady and buzzers off.
• If pre-alarm has been acknowledged and restores to normal, the condition clears. If the
system proceeds into an alarm condition, the pre-alarm condition clears whether or not
it has been acknowledged and is replaced by alarm.
General Alarm
To activate a general alarm, proceed as follows:
• Press "MENU".
• On the MENU display, select "GENERAL ALARM".
• At the next screen, select "Yes".
• Silence and reset the system as with any alarm.
Alert
To activate alert alarm, proceed as follows:
• Press "MENU".
• On the MENU display, select "ALERT".
• At the next screen, select "Yes".
• Operate ALARM SILENCE to terminate alert signal.