Siemens FS-250 Spécifications Page 39

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 68
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 38
FS-250 Installation and Operation Manual
33
Auxiliary Power Supply
*Connect a PAD-3 auxiliary supply when power requirement calculation indicates that an
additional source is required. For further information, refer to Appendix D.
Battery Size Calculations
For calculation of battery size requirements see Appendix A.
NAC Wiring
At the lower right corner of the main board are the terminal blocks (TB12, TB13) are used
for the connection of notification appliances. Four individual NACs marked 1 through 4 are
provided and the polarity shown is when the NAC is activated.
Use the following table to configure the NACs for either class A or class B operation.
NAC #s Class “B”
Operation
Paired Class
“A” Operation
1,2 JP1 JP2
3,4 JP3 JP4
NAC Rating:
A
larm Voltage: 24V FW nominal
Max. Alarm Current: 1.5A/NAC circuit
Max. Ripple: 16VAC
Max. Wire Voltage Drop: 1.0VDC
Max. Standby Current: 1.0mA
NOTE: The maximum total current for the FS-250
NACs is 3.0A and 6.0A with the optional additional
FS-NPE Transformer.
Typical Notification Appliance Circuit
Style Z, Class A
Supervised, Power Limited
See A
pp
endix B for Com
p
atible Devices
Typical Notification Appliance Circuit
Style Y, Class B
Supervised, Power Limited
See A
pp
endix B for Com
p
atible Devices
See Chart for NAC Jumper
Configurations
Polarity Shown
In activated Condition
Technical Manuals Online! - http://www.tech-man.com
Vue de la page 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 67 68

Commentaires sur ces manuels

Pas de commentaire