s Industry, Inc.
Building Technologies Division
FireFinder XLS Components ─ (cont.’d)
Each Model SCM-8 switch is fully programmable, and may
be used to control speaker circuits and a wide range of
general-system functions such as: All Call, All Evac,
Warden's Page, Speaker, etc. Any number of circuits may
be grouped and controlled by a single switch. Switch
usages and zone groupings are assigned using the Zeus
system software-programming software. Model SCM-8
modules are mounted on a hinged panel, as a part of the
FireFinder XLS Command Console enclosure.
LCM-8 LED Control Module
LCM-8 LED Control Module
The LED Control Module (Model LCM-8) is a FireFinder
XLS-option module that provides LED annunciation for
FireFinder XLS system activity. Each LCM-8 module
contains eight (8) groups of two (2) LEDs – each of which
can be assigned to desired outputs using the Zeus
system software-programming tool.
Eight (8) LEDs are dual-color capable (RED or GREEN /
flashing or steady). The remaining LEDs are AMBER
flashing or steady. A space is provided for labeling of LED
functions. The label slides behind a clear, protective
membrane. Model LCM-8 dimensions are identical to
Model SCM-8, and Model LCM-8 is mounted on the same
hinged panel, as a part of the FireFinder XLS Command
Console enclosure.
FCM-6 Fan, Motor, Dampers
Control Module
FCM-6 Fan, Motor, Dampers Control Module
The Fan, Motor, Dampers Control Module (Model FCM-6) is a
FireFinder XLS command-console option module that
provides manual control of building HVAC system fans,
motors, and dampers. Each Model FCM-6 module provides
six (6) sets of three (3) push-button switches for manual-
system control. Each switch has three (3), associated
LEDs to indicate Fan / Damper / Motor status: OFF (Red LED),
ON (Green LED), TROUBLE (Yellow LED).
PSC-12 Power Supply Charger Module
PSC-12 Power Supply Charger Module
The Power Supply Charger Module (Model PSC-12) is a
high-current power supply that provides the FireFinder
XLS primary-regulated 24VDC power to operate. Model
PSC-12 is rated at 12Amps (Alarm) / 5Amps (Standby), and
has a built-in battery charger, capable of charging up to 100
AH batteries. Model PSC-12 is an addressable-intelligent,
microprocessor-controlled module that communicates its
status to the system-operator interface (PMI). Model PMI is
able to query the status of the power supply to obtain
information regarding system-charging current, terminal-
loading information, ground-fault conditions and more.
PTB Power Termination Board
PTB Power Termination Board
Model PSC-12 comes packaged with a module called the
Power Termination Board (Model PTB). Model PTB is
required for operation with Model PSC-12. Model PTB filters
the power from the incoming AC mains, and distributes it
to the Model PSC-12 power supply and the optional Model
PSX-12 power-supply extender.
Model PTB has an optional connector that can be used during
system installation, commissioning and service to provide
the technician with a place to plug in their laptop PC, if
required. Model AC-ADPT is an optional accessory cable that
allows connection on one side to Model PTB, via a keyed
connector and on the other end directly into to the laptop's
transformer.
Most laptop-computer external power transformers have
removable AC power cords, which can be replaced by the
optional Model AC-ADPT to temporarily provide an AC
power source for laptop-PC usage during system
installation, service and maintenance calls when needed.
PSX-12 Power Supply Extender
PSX-12 Power Supply Extender
The Power Supply Extender (Model PSX-12) is a high-current,
auxiliary power supply that expands the main Model PSC-12
power supply and battery charger of the FireFinder XLS
system with an additional 24VDC power. Model PSX-12
is rated at 12 Amps.