FireFinder XLS Components ─ (cont.’d)
CRC-6 Controllable Relay Card
CRC-6 Controllable Relay Card
The Controllable Relay Card (Model CRC-6) is used with
the FireFinder XLS FACP. Model CRC-6 is designed to
provide auxiliary control of building functions, such as:
door-holder release, elevator capture, smoke control, lock
release, etc. Model CRC-6 plugs into one (1) slot in the
Model CC-5 or Model CC-2 card cage. Model CRC-6
provides six (6), fully programmable relays. Each relay
contains one (1) set of SPDT contacts rated at 4 Amps 30
VDC / 120VAC resistive and 3.5 amps 120VAC inductive (0.6
P.F.)
SIM-16 Supervised Input Module
SIM-16 Supervised Input Module
The Supervised input Module (Model S
IM-16) is a
remotely located, general-purpose input module. Model
S
IM-16 provides 16 input circuits for remote system
monitoring. Each input can be individually programmed
as supervised (dry-contact only) or unsupervised (general-
purpose input.) Model S
IM-16 has two (2) Form C relays.
The relays and inputs are programmed using the Zeus
system software-programming tool.
CDC-4 Conventional Detector Card
CDC-4 Conventional Detector Card
The Conventional Detector Card (Model CDC-4) is used
to monitor Siemens Fire Safety conventional detectors
on the FireFinder XLS system. Model CDC-4 can be
used in applications where conventional detectors are
more suited than addressable detectors, such as
hallways or large meeting rooms. Also, Model CDC-4
can be used to upgrade Siemens conventional fire-alarm
panels to the FireFinder XLS system without requiring
detector replacement.
CC-2 Card Cage-2 Slots CC-5 Card Cage-5 Slots
CC-5 / CC-2 Card Cages
The Models CC-5 / CC-2 card cages provide the physical
mounting location and all wiring connection points for all
fire-and-voice system options cards for the FireFinder XLS
system. Model CC-5 has five (5) slots, while Model CC-2
has two (2) slots.
All cards plugged into the CC-5 / CC-2 card cage
communicate with other FireFinder-XLS modules via a
common data bus. Connectors are provided on the left and
right side of the CC-5 to connect a 60-pin cable for
communications with the FireFinder-XLS' operator interface,
power supplies and amplifiers modules.
Field wiring to devices and circuits terminates on the
Models CC-5 / CC-2 card cages. All cards designed for use
with the Models CC-5 / CC-2 route their field wiring
terminations to the ‘top’ of the Model CC-5 / CC-2 card
cages. These connections are all power limited. Internal
wiring connections distribute 24VDC to cards or high-level
audio signals (depending on application used) connect to
the ‘bottom’ of the Model CC-5 / CC-2 card cages. These
connections are all non-power limited.
All wiring connections to the Model CC-5 / CC-2 card cages
are to removable terminal blocks. Terminal blocks are rated
for use with wire sized 12AWG to 24AWG. Each connector is
numbered to make wiring terminations to the correct
position on the terminal block simple in order to reduce
potential wiring errors.
SCM-8 Switch Control Module
SCM-8 Switch Control Module
The Switch Control Module (Model SCM-8) is a FireFinder
XLS-option module that provides manual control to the
Emergency Voice Evacuation System (EVAC) or manual
fire-system control. Each Model SCM-8 module provides
eight (8) momentary push-button switches and 16
light-emitting diodes (LEDs) to indicate their status.
Each switch is assigned two (2) LEDs, as well as a label
to indicate the switch's programmed usage. The label
slides behind a clear protective membrane. One of the
LEDs assigned to each switch is a dual-colored LED,
which is used to indicate what type of signal is active.