FireFinder XLS Components ─ (cont.’d)
Each circuit can be independently programmed for use
with listed audible or visual notification appliances, listed
emergency audio speakers, municipal tie boxes, leased
lines, or as releasing circuits. Model Z
IC-4A plugs into one
(1) slot in the Model CC-5 or Model CC-2 card cage, and has
on-board LEDs for system status and troubleshooting.
Indication of power, communication, internal operation,
and ground-fault conditions are provided, as well as
indication of circuit activation or Trouble conditions.
ZIC-8B / ZIC-2C Zone Indicating Cards
ZIC-8B / ZIC-2C
The Zone
Indicating Card (Model ZIC-8B) provides eight (8)
fully supervised, programmable output circuits for use on
the FireFinder XLS f
ire-alarm control panel (FACP). Model
Z
IC-8B supplies eight (8) Class B (Style Y) type output
circuits, power limited to 2.0 amps maximum per circuit.
Each circuit can be independently programmed for use
with listed audible or visual notification appliances, or
listed emergency audio speakers. Model Z
IC-8B plugs
into one (1) slot in the Model CC-5 or Model CC-2 card
cage, and has on-board LEDs for system status and
troubleshooting.
Model ZIC-2C mounts directly on Model ZIC-8B, and
allows each of the Model Z
IC-8B output circuits to be used
for two-channel voice applications.
Indication of power,
communication, internal operation, and ground-fault
conditions are provided, as well as indication of circuit
activation or trouble conditions.
NIC-C Network I nterface Card
NIC-C Network Interface Card
The Network
Interface Card (Model NIC-C) provides HNET or
XNET network communications between enclosures.
In
addition to the HNET or XNET communication, Model N
IC-C
provides CAN network communication within an enclosure
or external to the enclosure. HNET or XNET communication
can be wired Style 4 or Style 7, but the CAN network can
be wired Style 4 only.
When used for HNET communications, Model N
IC-C
provides communication between enclosures on a single
system.
When Model N
IC-C is used for XNET communications,
Model N
IC-C provides communication between systems.
The maximum of XNET Model N
IC-C cards on a single
system (single node) is one (1), for a total of 64 XNET
Model NIC-C cards on a peer-to-peer networked system.
Model N
IC-C has diagnostic LEDs that indicate: Card Fail,
CAN Fail, HNET Fail, XNET Fail, Ground Fault, Loop ‘A’ Fail and
Loop ‘B’ Fail. Model N
IC-C Card also has LEDs to indicate
Power, Style and Active Networks.
HLIM Line Isolator Module
HLIM Line Isolator Module
The loop-isolator module (Model HL
IM) provides short-
circuit protection on FireFinder XLS intelligent device
circuits (see: Model DLC). When Model HL
IM detects a
short circuit, Model HL
IM is able to isolate the affected
segment of the circuit – allowing the remaining devices
to continue operation. Model HL
IM is self-restoring –
automatically reconnecting to circuit segment when the
fault is removed. Model HL
IM can be wired in either a
Style 4 or Style 6 configuration.
Model HL
IM does not occupy a device address on the Model
DLC circuit, and does not require programming. Up to 15
Model HL
IM modules may be installed on each Model DLC
loop.
HCP Control Point Module
HCP Control Point Module
Model HCP provides an intelligent control point for the
FireFinder XLS Control Panel. Model HCP can be
programmed as an independent, remotely located tele-
phone zone, speaker zone or notification appliance
circuit. Model HCP is designed to be used with the
Siemens – Fire Safety Notification-Appliance Circuits
product line.
Model HCP communicates through the Model DLC
analog loop, and can be wired either Class A (Style Z) or
Class B (Style Y). The 24 VDC power input comes from
either the control panel or from any
UL Listed power-
limited, auxiliary-power supply.