5 Creating Project Files—Modbus Master to Devices
42 Siemens Energy & Automation, Inc.
The relevant status codes (Text #) are listed below.
Table 5.1 7SJ600 Relay Information
For Requesting Status of the 7SJ600 Relay’s Three Binary Inputs
Text Number/Status Code
(default value returned if
not converted)
Description of Returned Binary
Input Status Codes: I1
indicates Input 1; I2,3 indicates
Inputs 2 and 3
Suggested Value (Using This Conversion Table)
Value
Inputs I3 I2 I1
00 000
1342 I1,2 Inactive : I3 Active 4 0 1 0 0
1343 I1,3 Inactive : I2 Active 2 0 0 1 0
1344 I1 Inactive : I2,3 Active 6 0 1 1 0
1345 I2,3 Inactive : I1 Active 1 0 0 0 1
1346 I2 Inactive : I1,3 Active 5 0 1 0 1
1347 I3 Inactive : I1,2 Active 3 0 0 1 1
1348 I1,2,3 Active 7 0 1 1 1
For Requesting Status of the 7SJ600 Relay’s Two Trip Contacts and Two Signal Contacts
Text Number/Status Code
(default value returned if
not converted)
Description of Returned Trip
and Signal Relay Status
Codes: S1,2 indicates Signal
Relays 1 and 2; T1,2 indicates
Trip Relays 1 and 2
Suggested Value (Using This Conversion Table)
Value
Outputs S2S1T2T1
Bits 15 . . . 43210
1349 S1,2 T1,2 Open 0 0 0000
1350 S1,2 T1 Open : T2 Closed 2 0 0010
1351 S1,2 T2 open : T1 Closed 1 0 0001
1352 S1,2 Open : T1,2 Closed 3 0 0011
1353 S1 T1,2 Open : S2 Closed 8 0 1000
1354 S1 T1 Open : S2 T2 Closed 10 0 1010
1355 S1 T2 Open : S2 T1 Closed 9 0 1001
1356 S1 Open : S2 T1,2 Closed 11 0 1011
1357 S2 T1,2 Open : S1 Closed 4 0 0100
1358 S2 T1 Open : S1 T2 Closed 6 0 0110
1359 S2 T2 Open : S1 T1 Closed 5 0 0101
1360 S2 Open : S1 T1,2 Closed 7 0 0111
1361 T1,2 Open : S1,2 Closed 12 0 1100
1362 T1 Open : S1,2 T2 Closed 14 0 1110
1363 T2 Open : S1,2 T1 Closed 13 0 1101
1364 S1,2 T1,2 Closed 15 0 1111
For Requesting Status of the 7SJ600 Relay’s Four Programmable LEDs
Text Number/Status Code
(default value returned if
not converted)
Description of Returned LED
Status Codes: L1,2 indicates
LEDs 1 and 2
Suggested Value (Using This Conversion Table)
Value
Outputs L4L3L2L1
Bits 15 . . . 43210
1365 L1,2,3,4 Off 0 0 0000
1366 L4 On : L1,2,3 Off 8 0 1000
1367 L3 On : L1,2,4 Off 4 0 0100
1368 L3,4 On : L1,2 Off 12 0 1100
1369 L2 On : L1,3,4 Off 2 0 0010
1370 L2,4 On : L1,3 Off 10 0 1010
1371 L2,3 On : L1,4 Off 6 0 0110
Vue de la page 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 140 141

Commentaires sur ces manuels

Pas de commentaire

Puls CD5.243 manuels

Manuels d'utilisation et guides de l'utilisateur pour Accessoires pour les appareils électriques Puls CD5.243.
Nous fournissons des manuels en pdf 1 Puls CD5.243 à télécharger gratuitement par type de document : Manuel de l'utilisateur






Plus de produits et de manuels pour Accessoires pour les appareils électriques Puls

Modèles Type de document
Aucun