8. Technical data
No internal fuse
External preliminary
protection with max. C 10 A circuit breaker
Q1, Q2, Q3 – N
Rating min, max resistive (inductive)
No internal fuse
External preliminary protection with max. C 10 A c
ircuit breaker in the supply line
required under all circumstances
Fans must NOT be connected in parallel!
Connect one fan directly, for additional fans, one relay for each speed.
Y1, Y2, Y3, Y4-N
Power limitation
Solid state (Triac)
AC 230 V, 8mA...1 A
A fast microfuse, cannot
X1-M / X2-M
Temperature sensor input
Type
Temperature range
Cable length
Digital input
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
D1-GND
Operating action
Contact sensing
Parallel connection of several
thermostats for one switch
Insulation against mains
Max. 20 thermostats per
switch.
Do not mix with
SELV DC 6…15 V, 3…6 mA
Max. 20 thermostats per
switch.
3.75 kV, reinforced
insulation
External temperature sensor, heating/cooling
changeover sensor, operating mode switchover
contact, dewpoint monitor contact, enable electric
heater contact, fault contact, monitoring input
X1: P38
X2: P40
D1: P42
Note!
95 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Technical data 2014-05-23