ACS offers plant diagrams for easy monitoring and operation of the thermostat.
To start this application, select Applications, then Pant diagram.
ACS provides standard plant diagrams for RDG KNX thermostats, which depend
on the configuration as follows:
Plant type
Application
Configuration
Application
Configuration
2-pipe
2-pipe fan coil unit
Control sequence: No impact (P01 = any)
Fan operation: Not disabled (P52 <> 0)
Radiator
Control sequence: Heating only (P01 = 0)
Fan operation: Disabled (P52 = 0)
Chilled / heated ceiling
Control sequence: Changeover (P01 = 2,3)
– Fan operation: Disabled (P52 = 0)
Chilled ceiling
Control sequence: Cooling only (P01 = 1)
Fan operation: Disabled (P52 = 0)
Plant diagram in ACS
86 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Supported KNX tools 2014-05-23