Fault
information
6 Fault Digital input to signal an external fault (example: dirty
air filter).
If the input is active, "ALx" is displayed and a fault is
sent on the bus. See also section 3.11.8.
(Alarm x, with x = 1 for X1, x = 2 for X2, x = 3 for D1).
Note: Fault displays have no impact on the
thermostat's operation. They merely represent a
DI DI
D1, X1, X2
(Digital)
7 Monitor input
(Digital)
Digital input to monitor the state of an external switch
via bus.
DI DI
X1, X2
8 Monitor input
(Temperature)
Sensor input to monitor the state of an external
sensor (e.g. QAH11.1) via bus.
AI --
X1, X2
(Temp.)
9 Supply air
temperature
limitation
(RDG160KN
Sensor input to acquire the supply air temperature.
The thermostat controls the room temperature via the
built-in sensor. The control output (DC 0...10 V) is
reduced if the supply air temperature exceeds the min
AI --
• Operational action can be changed between normally open (NO) and normally
closed (NC) via parameter P39, P41 (or P43 if it is a digital input).
• Each input X1, X2 or D1 must be configured with a different function (1…5).
Exception: 1, 2 or 3 inputs can be configured as fault (6) or monitor input (7,8).
• X1 is factory-set to "External sensor" (1), X2 to "Not used" (0), and D1 to
"Operating mode switchover" (3).
For more detailed information, refer to section 3.4 "Applications".
• For inputs X1, X2, or D1, one physical switch can be used for up to 20
thermostats (parallel connection).
Caution! DO NOT mix X1 / X2 (mains potential on RDG100KN) and D1.
• For sensors on inputs X1, X2, or D1, the cable length is max. 80 m.
59 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23