Dew point monitoring is essential to prevent condensation on the chilled ceiling
(cooling with fan disabled, parameter P52). It helps avoid associated damage to
the building.
A dew point sensor with a potential-free contact is connected to multifunctional
input X1, X2 or D1. If there is condensation, the cooling valve is fully closed until no
more condensation is detected, and the cooling output is disabled temporarily.
The condensation symbol " " is displayed during temporary override and the fault
"Condensation in room" will be sent via bus.
The input must be commissioned accordingly (P38, P40, P42).
See section 3.9 "Multifunctional input".
If the "Button lock" function is enabled by parameter P14, the buttons will be locked
or unlocked by pressing the right button for 3 seconds.
If "Auto lock" is configured, the thermostat will automatically lock the buttons 10
seconds after the last adjustment.
The external equipment (e.g. fan coil unit) can be switched off via relay output Q3
of the thermostat, in order to reduce energy consumption when the thermostat is in
Protection mode and no temperature control is requested.
The "Switch off in Protection" function is enabled via parameter P74 = 1.
The relay function can be checked via diagnostic parameter d10.
This function is only available for applications with DC 0…10 V fan (DIP 4 = off or
P53 = 3), or for universal applications (without fan).
off external
equipment in
Protection mode
(RDG160KN)
31 / 102
Siemens RDG100KN, RDG160KN Basic documentation CE1P3191en
Building Technologies Functions 2014-05-23