Overview of the DP Base Interface
DP Base Programming Interface for CP 5613/CP 5614
48
C79000-G8976-C108-01
Shutdown Sequence
Shutting down the CP brings the DP master to the OFFLINE mode and is
completed by stopping the CP:
Step Action Meaning
1 DP_set_mode(Clear) Bring the master to the CLEAR mode, the
slaves are reset.
2 DP_set_mode(Stop)
Bring the master to the STOP mode, cyclic
operation is terminated.
3 DP_set_mode(Offline) Bring the master to the OFFLINE mode.
4 DP_release_pointer Enable access to the process image.
5 DP_close Log off.
6 DP_reset_cp Stop the CP.